Abstract

This article examines the impact of high-power six-phase valve-controlled converters used in metallurgical production on the power quality of the enterprise's power grid. The operating principles and main sources of nonsinusoidality characteristic of these devices are discussed, particularly switching distortions and the generated spectrum of higher harmonics. The results of instrumental measurements of current and voltage harmonic components, performed at the main step-down substation using a PKK-57 device, are presented. A qualitative and quantitative spectrum analysis was performed, confirming the presence of harmonics of the 5th, 7th, 11th, and 13th orders, which corresponds to theoretical expectations for six-pulse circuits. It was established that the voltage harmonic level is within acceptable limits, while harmonic current distortion is significant. Based on statistical data processing using the least-squares method, polynomial models for predicting harmonic levels were developed. A conclusion is drawn regarding the need for continuous monitoring and the potential installation of filter-compensating devices to ensure electromagnetic compatibility.