NobleBlocks

Research indexJournal article

Unit commitment optimization method considering transient voltage stability and frequency security

Shuo, Zikang, Jinquan and 2 others

Zhejiang dianli1 Oct 2026Open access

NobleIDark:/48914/w1/20261105/1E7C2F0FDOI10.19585/j.zjdl.202610002

Abstract

To address the decline in transient voltage stability and frequency security margins caused by the high penetration of renewable energy, this paper presents an optimized unit commitment (UC) method that incorporates both transient voltage stability and frequency security. First, a grid sample database is established to extract steady-state features that influence transient voltage stability, with corresponding transient characteristics obtained through batch time-domain simulations. Subsequently, symbolic regression is applied to perform coefficient fitting on key feature variables, thereby constructing transient voltage stability constraints suitable for model embedding. Then, frequency security constraints are formulated based on the rate of change of frequency (RoCoF), frequency nadir, and quasi-steady-state frequency boundaries. These two sets of stability constraints are then embedded into the UC framework to enable a computationally efficient solution for unit start-stop schedules. Finally, simulation analysis based on a modified IEEE 39-bus system demonstrates that the proposed method effectively enhances the stability margins of the grid and guarantees its secure and stable operation.

Discussion

Topics

More

Suggest a correction or report